Key features- Type 1+2+3 combined surge protective device (SPD) based on gas-filled spark gap (VG technology)
- 10-year guarantee
- Discharge capacity per pole: Iimp = 12.5 kA (10/350 µs)
- Nominal discharge current In: 20 kA (15 x 8/20 µs)
- Safe disconnection (failsafe mode) with mechanical indicator per pole
- No operating or leakage follow current
- Suitable for lightning protection classes III + IV; compliant with VDE-AR-N 4100 use in main supply systems
- Plug-in modular format for cost-effective maintenance; spare module MDAC1-13VG-275 available
- Complies with IEC 61643-11 / EN 61643-11 and UL1449 5th ed.; KEMA certified
DescriptionThe ZPAC1-13VG-30-275 is a space-saving, plug-in Type 1+2+3 SPD designed for 230/400 V three-phase systems and installation on 40 mm busbar systems. Integrating CITEL VG technology (MOV + gas-filled spark gap), it combines all three protection classes in a single device to provide robust surge protection for downstream equipment and meets the minimum Type 1 lightning current requirements (Iimp 12.5 kA, 10/350 µs). Its design allows use in buildings requiring lightning protection classes III and IV and enables installation in the pre-metering area where applicable. The modular plug-in concept simplifies on-site maintenance and replacement, reducing downtime for electrical contractors and facility managers.
Documents available (names)- Datasheet
- CITEL_Certif_KEMA_ZPAC1-13VG.pdf
- CITEL_Certif_CB_ZPAC-13VG.pdf
- Installation Manual
Technical specifications- SPD type (IEC): 1+2+3
- Network: 230/400 V 3-phase
- AC system: TNC
- Nominal line voltage (Un): 230/400 Vac
- Max. AC operating voltage (Uc): 275 Vac
- Temporary Over Voltage (TOV) - 5 sec. (UT): withstand 335 Vac (without disconnection)
- Temporary Over Voltage (TOV) - 120 min (UT): withstand 440 Vac (without disconnection or with safety disconnection)
- Residual current (leakage to ground) (Ipe): None
- Operating current (Ic) at Uc: None
- Follow current: None
- Nominal discharge current (In) 15 x 8/20 µs: 20 kA
- Max. discharge current (Imax) max. withstand @ 8/20 µs per pole: 50 kA
- Impulse current per pole (Iimp) max. withstand 10/350 µs: 12.5 kA
- Total lightning current (Itotal) max. total withstand @ 10/350 µs: 37.5 kA
- Withstand on Combination waveform IEC 61643-11 (Uoc): 6 kV
- Specific energy per pole W/R (max. withstand 10/350 µs): 40 kJ/ohm
- Protection mode(s): L/PE
- Protection level L/PE (Up @ In (8/20 µs)): 1.5 kV
- Residual voltage L/PE at 5 kA (Up-5kA): 0.9 kV
- Admissible short-circuit current (Isccr): 50 000 A
- Technology: VG Technology (MOV + GSG)
- SPD configuration: 3-phase
- Connection to network: By 40 mm busbar and wire for PE: 6-35 mm² (50 mm²)
- Format: Plug-in modular box
- Mounting: 40 mm busbar systems
- Housing material: Thermoplastic UL94 V-0
- Operating temperature (Tu): -40 / +85 °C
- Protection rating: IP20
- Outdoor application: No
- Failsafe mode: Disconnection from AC network
- Disconnection indicator: 1 mechanical indicator per pole
- Spare module(s): MDAC1-13VG-275
- Remote signaling of disconnection: none
- Dimensions: See diagram
- Weight: 0.677 kg
- Standards compliance: IEC 61643-11 / EN 61643-11 / UL1449 5ed.
- Certification: KEMA