The DACN15-P surge protectors are designed for single-phase low-voltage AC installations. They provide Type 2+3 protection with a nominal discharge current (In) of 5 kA and a maximum discharge current (Imax) of 15 kA. In accordance with IEC standards, units with In = 5 kA can be installed in main or secondary distribution panels. The DACN15-P11-275/INV variant features an inverted base for bottom wiring to suit specific installation constraints.
Key features- Type 2 or 3 surge protection (IEC 2+3)
- Compact single-phase monobloc module
- Nominal discharge current In: 5 kA (8/20 µs)
- Maximum discharge current Imax: 15 kA (8/20 µs)
- Protection modes: L/N and N/PE (common and differential)
- Bottom connection by screw terminals (1.5–10 mm²)
- Compliance: EN 61643-11, IEC 61643-11, UL1449 ed.5
Electrical propertiesSPD type: 2+3 (IEC)
Network: 230/400 V
AC system: TT / TN
Max. AC operating voltage (Uc): 275 Vac
TOV 5 s (UT): 335 Vac withstand (no disconnection)
TOV 120 min (UT): 440 Vac disconnection (with or without safety disconnection)
TOV N/PE (HT): 1200 V / 300 A / 200 ms withstand
Residual/leakage current to earth (Ipe): None
Follow current: None
Nominal discharge current In (15 x 8/20 µs): 5 kA
Max. discharge current Imax per pole (8/20 µs): 15 kA
Combination waveform Uoc (IEC 61643-11 class III): 10 kV
Protection level Up L/N @ In (8/20 µs): 1.1 kV
Protection level Up N/PE @ In (8/20 µs): 1.5 kV
Admissible short-circuit current (Isccr): 10 000 A
Mechanical propertiesTechnology: MOV + GDT
SPD configuration: Single-phase
Connection to network: Bottom connection, screw terminals 1.5–10 mm²
Format: Monobloc modular box (compact)
Pluggable: No
Mounting: Symmetrical DIN rail 35 mm (EN 60715)
Housing material: Thermoplastic UL94 V-0
Operating temperature (Tu): -40 °C to +85 °C
Protection rating: IP20
Failsafe mode: Internal disconnection from AC network
Disconnection indicator: Green LED OFF (end-of-life indication)
Dimensions: 1TE (EN43880) — see diagram
Weight: 0.093 kg
Accessories / Recommended disconnectorsThermal disconnector: Internal
Installation residual-current device (if present): Type S or time-delayed
Recommended isolation fuse for disconnection: min. 20 A — max. 125 A, fuse type gG
StandardsIEC 61643-11 / EN 61643-11 / UL1449 ed.5
Technical specifications- Product reference: DACN15-P11-275/INV
- Product code: 70146023
- SPD type: 2+3 (IEC)
- Network: 230/400 V
- AC system: TT / TN
- Uc (max. operating voltage): 275 Vac
- TOV 5 s: 335 Vac withstand
- TOV 120 min: 440 Vac disconnection
- TOV N/PE: 1200 V / 300 A / 200 ms withstand
- In (8/20 µs): 5 kA
- Imax (8/20 µs per pole): 15 kA
- Combination waveform Uoc: 10 kV (class III)
- Up L/N @ In: 1.1 kV
- Up N/PE @ In: 1.5 kV
- Isccr: 10 000 A
- Technology: MOV + GDT
- Connection: Bottom, screw terminals 1.5–10 mm²
- Mounting: DIN rail 35 mm (EN 60715)
- Housing: Thermoplastic UL94 V-0, monobloc modular format
- Operating temperature: -40 to +85 °C
- IP rating: IP20
- Failsafe: Internal disconnection from AC network
- End-of-life indicator: Green LED OFF
- Dimensions: 1TE (EN43880)
- Weight: 0.093 kg
- Compliance: IEC 61643-11 / EN 61643-11 / UL1449 ed.5