Product informationAnalog hand-control module with emergency function for 1 or 2 analog outputs (0–10 V). Provides manual override of controller or DDC outputs. The rotary selector ('Auto' / 'Close' / 'Open' / 'Pot') selects the operating mode: in 'Auto' the control system determines the output; in 'Pot' the built-in potentiometer sets the output continuously between 0 and 10 V. The current output level is indicated on the bar display. Terminal 43 supplies 10 V DC (e.g. for frost control). Each output is loadable up to 10 mA. The 'Auto' position of each switch is provided potential-free on a terminal. If local status feedback (Close‑Open potentiometer) is required, specify type suffix -H0. Variants: RAG0015 = 1 analog output, RAG1515 = 2 analog outputs.
Features- Hand-control level with emergency function for 1 or 2 analog outputs (0–10 V)
- Rotary selector with positions: Auto / Close / Open / Pot
- In 'Pot' position: continuous adjustment of the output signal 0–10 V via built-in potentiometer
- Bar display for visual indication of the output voltage
- Terminal 43 provides 10 V DC (e.g. for frost control)
- Outputs loadable up to 10 mA each
- 'Auto' position of each switch available potential-free on a terminal
- Specify type suffix -H0 when local status feedback (Close‑Open potentiometer) is required
- Variants: RAG0015 = 1 output, RAG1515 = 2 outputs
Technical specifications- Model / Commercial designation: RAG1515-H0
- Manufacturer / Brand: romutec Steuer- und Regelsysteme GmbH
- Product number / SKU: 00001735
- Output signal: 0–10 V (analog)
- Number of outputs: 2 (RAG1515); 1 (RAG0015 variant)
- Output load capacity: up to 10 mA per output
- Potentiometer: integrated, continuous adjustment 0–10 V
- Bar display: present, indicates output voltage
- Auxiliary terminal 43: 10 V DC available
- 'Auto' position: potential-free on terminal
- Type suffix for local feedback: -H0
- Weight (meta): 0.141 kg
- Release date (meta): 2026-04-28