Compact and efficient, the MSC-M4 energy measurement module allows for comprehensive analysis of a three-phase/four-wire circuit or three single-phase circuits:
- **Main Features:**
- Auxiliary power supply: 80 to 270V AC/DC.
- Connection of 3 Enerclip current transformers: closed, opening, or Rogowski loops, to measure 1 three-phase/four-wire circuit or 3 single-phase circuits.
- **High Precision Measurement:**
- Active energy class 0.5S
- Reactive and apparent energies
- Voltage, current class 0.2
- Power, PF class 0.5
- Harmonics up to the 31st order class A
- **Installation and Connection:**
- 1-module width housing, DIN rail mountable.
- Connection:
- Current sensors via RJ12 cable
- Voltage connections on pluggable screw terminal block
- Auxiliary power supply and RS485 port on pluggable screw terminal block
- **Extension Module:**
- An MSC-ME module can be associated with the MSC-M4 measurement module to add the following features:
- Temperature measurements.
- Relay outputs controllable via Modbus or programmable on reaching minimum or maximum thresholds of current, power, voltage, temperature, etc.
- Digital inputs
- These MSC-ME extension modules allow interaction with the electrical circuits of the cabinet.
- **Functionalities:**
- Measurement of main electrical quantities for detailed circuit analysis:
- Active and reactive energies, imported and exported
- Multi-tariff counting
- Voltage
- Current
- Active, reactive, and apparent powers
- Power factor
- Frequency
- Demands
- Extreme values
- Average values
- Harmonic distortion rate U and I
- Harmonics up to the 31st order
- Imbalances...
- Control of electrical circuits:
- The relay outputs and digital inputs of the extension modules allow control of electrical circuits based on measured values or external events.
- Programmable relay outputs can ensure automation functions, alarm triggers, load shedding, etc.
- Digital inputs are generally used to report the status of external electrical circuits in Modbus or to count and communicate the number of pulses emitted by a water or gas meter.
- Energy performance monitoring:
- By associating temperature and electrical consumption measurements, Enerclip V2 allows monitoring of the energy performance of buildings and infrastructures.
- **Associated Products:**
- Displays: The measurements of a large number of Enerclip MSC-M4 modules can be interfaced on the flush-mounted displays MSC-DE-2 and MSC-DE-4, as well as on the free Enerclip V2 software.
- Current transformers: All Enerclip current sensors are connected to the measurement module via an RJ12 cable:
- 3 closed current transformers, up to 600A, connected by a triple RJ12 cable.
- 3 opening current transformers, up to 600A, connected to an MSC-TCO-TRI connector, itself connected to the measurement module via a simple RJ12 cable.
- 3 opening and flexible Rogowski loops, up to 3000A, connected to an MSC-TCR-TRI connector, itself connected to the measurement module via a simple RJ12 cable.
- Measurement center compatible with Enerclip current transformers:
- Closed CTs: MSC-TCF
- Open CTs: MSC-TCO
- Rogowski loops: MSC-TCR
- Compatible with: MSC-DE-4 or MSC-DE-2, associated with the MSC-C1 communication module.
- **Advantages:**
- A measurement center in a 1-module housing!
- Easy connection with CTs connected via RJ12 cable and other connections on pluggable terminal blocks.
- **Standards and Certifications:**
- CE, RoHS, REACh.
- **Variants and Order Codes:**
- Order Code | Module Function | Product Stocked
- MSC-M4 | Main module – Electrical measurements | instock
- MSC-ME0 | 4 temperature probes | instock
- MSC-ME1 | 4 temperature probes and 3 digital inputs | instock
- MSC-ME4 | 4 temperature probes and 4 relay outputs | instock
- MSC-ME10 | 4 temperature probes, 3 digital inputs, 1 relay output, and 1 insulation controller | instock
- **Characteristics / Technical Specifications:**
- Auxiliary power supply: 80 to 270V AC/DC
- Connection of 3 Enerclip current transformers (closed, opening, or Rogowski loops)
- Measure 1 three-phase/four-wire circuit or 3 single-phase circuits
- Active energy class 0.5S
- Voltage, current class 0.2
- Power, PF class 0.5
- Harmonics up to the 31st order class A
- 1-module width housing, DIN rail mountable
- Current sensors via RJ12 cable
- Voltage connections on pluggable screw terminal block
- RS485 port on pluggable screw terminal block
- Available extension modules: temperature measurements, relay outputs, digital inputs, insulation controller
- Compliances: CE, RoHS, REACh