Product features- Selectable up to 7 tone modes.
- Independent base for simplified installation, commissioning and maintenance.
- High-brightness LEDs for conspicuous visual signalling, long life and low power consumption.
- Optional tamper-evident function.
Product Info C9092T Conventional Sounder Beacon is designed for use with conventional fire alarm control panels. It provides audible and visual alarm indication at incident locations and is suitable for high-rise residential buildings, public places, hotels, entertainment venues, factories, shopping centres, hospitals, schools, office buildings and areas with low visibility or possible smoke generation.
Technical Parameters- Power supply: see working voltage
- Executive standard: EN54-3 (Type A)
- Working voltage: DC24V (tolerance DC20V–28V)
- Power consumption: ≤0.2W @ DC24V
- Alarm current: 1mA–8mA @ DC24V
- Wiring method: Non-polarity, two-core cable
- Operating temperature: -10°C to +55°C (indoor)
- Relative humidity: ≤95% (at 40°C, without condensation)
- Flash rate: 1–1.5 Hz
- Maximum sound output: ≥90 dB(A) @1 m (Tone 1)
- Tone type: 7 user-selectable tones (EN54-3 approved for Tone 1 only)
- Installation: Ceiling mounted
- Material (lens/body): Flame-retardant PC/ABS
- Weight: About 130 g (with base)
- Ingress protection: IP21C
- Dimensions: 111 × 111 × 50 mm (with base)
Specifications- Std: EN54-3 (Type A)
- Voltage: DC24V (DC20V–28V)
- Current: 1mA–8mA (alarm)
- Sound output: ≥90 dB(A) @1 m
- Flash rate: 1–1.5 Hz
- Mounting: Ceiling
- Protection: IP21C
- Weight/dimensions: ~130 g / 111×111×50 mm