Product overviewThe A9056T I/O module is designed to work with the SEC3002 fire alarm control panel. It provides output control for fire-linkage equipment (smoke dampers, blow valves, fire dampers) and monitors feedback signals to verify equipment operation. The module is supplied with a mounting base and holds LPCB and CPR approvals under EN54-18.
Key features- LPCB and CPR approval (EN54-18)
- Two LED indicators (Monitor / Output) for clear status indication
- Built-in terminal resistor
- Jumper-selectable normally open / normally closed contact
- Low loop and power consumption for minimal impact on panel loop
- Output contact capacity <2A @ DC30V
Technical specifications- Standard: EN54-18
- Operating voltage: loop DC24V (non-polarity); power DC24V (non-polarity)
- Static current: loop <0.8 mA; power <2 mA
- Action current: loop <5 mA; power <15 mA
- Output contact capacity: <2A @ DC30V
- Indicator behaviour: inspection LED blinks ~every 12 s; output LED steady when active; input LED lit on feedback
- Operating environment: indoor, temperature -10℃ to 55℃; RH ≤95% (40℃±2℃, non-condensing)
- Dimensions: 86×86×41 mm (with base)
- Weight: approx. 148 g (with base)
Applications and compatibility- Designed for use with SEC3002 fire alarm control panel
- Controls smoke dampers, blow valves, fire dampers and other fire-linkage devices
- Suitable for indoor fire detection and suppression system installations
Installation and maintenance- Mounts on supplied base for panel or enclosure installation
- Wiring: loop and power DC24V non-polarized; follow SEC3002 wiring diagrams
- Select NO/NC via jumper according to the controlled device
- Check LED indicators and wiring during commissioning and scheduled maintenance
Ordering information- Model: A9056T (supplied with base)
- Standards and approvals: EN54-18; LPCB, CPR
- For technical drawings, installation instructions or spare parts, request documentation from your supplier