OverviewThe SEC1000 addressable Fire Alarm Control Panel (FACP) monitors input signals, indicates events and activates outputs as programmed. Designed for simplified installation, operation and maintenance, it is built to comply with EN 54-2 and supports integration into multi-panel networks.
Key features- One loop supporting up to 120 addressable points.
- Supports loop wiring Class A (fault-tolerant) and Class B.
- 4.3" colour LCD (480×272) for clear system status and menus.
- 16 zone indicators for rapid alarm localisation.
- Event logging: 1000 records for historical fire, fault and operation events.
- Independently programmable conventional sounder circuit output (S.C.Out).
- Integral power supply with battery backup and onboard charger.
- Front-panel cause-and-effect programming with intuitive interface.
- Commissioning aids: zone test, point test and module start/stop functions.
- U-disk interface for convenient configuration backup/restore and data export.
- Three-level hierarchy access control for secure operation.
- Physical anti-tamper protection via key lock.
- CAN bus for interconnection of up to 20 panels.
Product infoThe SEC1000 is an addressable detection panel with one loop of up to 120 addressable devices and expansion capability via communication buses. It is compatible with other Sanjiang peripherals using the manufacturer's protocol and is suitable for commercial and industrial fire detection installations requiring EN54-2 compliance.
Technical Parameters:Mains supply: 110V/230VAC (-15%, +10%), 50Hz/60Hz.
Mains fuse: T3.15AL250V.
Operating voltage: 20 ~ 28VDC.
Recommended mains cable: standard black mains cable, 0.75mm².
Power rating: Imin = 0.45A; Imax.a = 1.15A; Imax.b = 1.65A.
Max. battery supply current: 3A (when mains disconnected).
Max. charging current: 1A.
Battery capacity, type and recommended model: NP7-12 for 7Ah VRLA (Yuasa).
Max. internal resistance of battery: 1Ω.
Battery fuse: F6AL250V.
Quiescent current (fully loaded): < 0.4A.
S.C.Out (+, -): Output voltage 20 ~ 28VDC; Max. output current: 800mA (1A S.C.Out + 24VK total); End-of-line resistor: 47KΩ 0.25W; Recommended cable: plain unscreened 1.5mm²; Cable diameter: 1mm² ~ 2.5mm²; Transmission distance: ≤1500m.
F.A. Out (+, -): Output voltage 20 ~ 28VDC; Max. output current: 100mA; End-of-line resistor: 47KΩ 0.25W; Recommended cable: plain unscreened 1.5mm²; Transmission distance: ≤1500m.
FAULT OUT (COM, NO): Contact capacity: 30VDC @ 2A, 125VAC @ 0.5A.
24VK (+, -): Recommended cable: plain unscreened 1.5mm²; Output voltage: 20 ~ 28VDC; Max. output current: 500mA (1A S.C.Out + 24VK total).
LOOP OUT / LOOP IN (+, -): Output voltage 18.5 ~ 28VDC (pulse); Max. output current: 500mA; Loop type: Class A and Class B; Recommended cable: unscreened twisted-pair 1.5mm²; Max. loop length: 2000m (Class A); Cable diameter: 1mm² ~ 2.5mm².
RS-485: Transmission rate 9600 bps; Recommended cable: unscreened twisted-pair 1mm²; Transmission distance: ≤1000m.
CAN: Max. number of panels: 20; Transmission rates optional: 10K, 20K, 50K, 100K bps; Recommended cable: unscreened twisted-pair 1mm²; Transmission distance: ≤1000m.
Approx. dimensions (W×H×D): 400 × 360 × 104 mm.
Approx. weight (without battery): 3.7 kg.
Operating conditions: Temperature range -5°C ~ 45°C; Max relative humidity: 95% (40°C ± 2°C, no condensation).
Specifications- Mains supply: 110V/230VAC (-15%, +10%), 50/60Hz
- Operating voltage: 20–28 VDC
- Loop capacity: 1 loop, up to 120 addressable points
- Zone indicators: 16 zones
- Display: 4.3" colour LCD, 480×272 resolution
- Battery: NP7-12 (7Ah VRLA recommended); Max charging current 1A; Max battery supply current 3A
- Outputs: S.C.Out up to 800mA; F.A. Out up to 100mA; 24VK output up to 500mA
- Communications: RS-485 (9600 bps), CAN (up to 20 panels, multiple rates)
- Dimensions: 400×360×104 mm; Weight (without battery): 3.7 kg