ProductFire alarm control panel SEC3004
Product features- Certified to EN54-2 & EN54-4 by LPCB and Applus.
- 7.0 inch colour touch-sensitive LCD, resolution 800×480.
- Supports 324 addresses per loop, up to 4 loops per panel.
- Supports up to 5000 fire protection zones.
- Night Mode time range settings for user-friendly operation.
- Networkable: CAN bus interconnection up to 60 FACPs; Ethernet interconnection up to 254 FACPs.
- Event logging: Fire alarm, fault, C&E and operation categories; each category can store up to 10,000 records.
Product infoThe SEC3004 control panels are touch-sensitive, addressable fire detection panels designed for simple installation, easy operation and easy maintenance. The SEC3004 provides up to 4 circuits (loops) with support for up to 324 addressable points per loop and is designed to meet EN54-2 & EN54-4 requirements.
Technical ParametersPower supply / Mains supply: 110V/230V AC (-15%, +10%), 50Hz/60Hz.
Mains fuse: T4A 250V.
Operating voltage: 28V ±0.5V DC.
Recommended mains cable: Standard/black mains cable, cable size 1 mm².
Power rating: Imax.a = 3.1A; Imax.b = 5.55A; Imin = 0.3A.
Max. battery supply current: 8A (when Mains is disconnected).
Max. charging current: 1A.
Physical dimensions: 440×400×180 mm (2×12V/12Ah Battery).
Max. internal resistance of battery: 1 Ω.
Approx. weight (without battery): 9 Kg.
Battery fuse: 15A.
Quiescent current (full loaded): <0.3A.
OutputsS.C.Out (+, -): Output voltage 20~28V DC; Max. output current 1A; End of line resistor 10 KΩ; Cable diameter 1 mm² ~ 2.5 mm².
F.A.Out (+, -): Output voltage 20~28V DC; Max. output current 50 mA; End of line resistor 10 KΩ; Cable diameter 1 mm² ~ 2.5 mm².
Fault Out (NC, COM, NO): Contact capacity 2A @ 24V DC; Cable diameter 1 mm² ~ 2.5 mm².
AUX 24V (+, -): Output voltage 20~28V DC; Max. output current 2A; Cable diameter 1 mm² ~ 2.5 mm².
Technical specifications- Certifications: EN54-2 & EN54-4 (LPCB, Applus).
- Display: 7.0" touch-sensitive colour LCD, 800×480 resolution.
- Addressing: 324 addresses per loop; up to 4 loops.
- Zones: Up to 5000 fire protection zones supported.
- Networking: CAN bus (up to 60 FACPs), Ethernet (up to 254 FACPs).
- Event log capacity: up to 10,000 records per category (fire alarm, fault, C&E, operation).
- Power: 110/230V AC mains; operating 28V ±0.5V DC.
- Battery/charging: Max battery supply current 8A (mains off); max charging current 1A; battery fuse 15A; max internal battery resistance 1Ω.
- Power rating: Imax.a = 3.1A; Imax.b = 5.55A; Imin = 0.3A.
- Dimensions: 440×400×180 mm (with 2×12V/12Ah batteries).
- Weight: approx. 9 Kg (without battery).
- Outputs and wiring: S.C.Out 20~28V DC (1A); F.A.Out 20~28V DC (50 mA); AUX 24V 20~28V DC (2A); Fault output contacts 2A @ 24V DC; recommended cable diameter 1 mm² ~ 2.5 mm²; EOL resistors: 10 KΩ where specified.