Product OverviewThe SEC3008 is an addressable, touch-sensitive fire alarm control panel compliant with EN54-2 & EN54-4. It is engineered for flexible loop capacity, networkability and detailed event logging to support commercial and industrial fire detection installations.
Product InfoThe SEC3008 supports up to 324 addressable points per loop and up to 8 loops per panel. The user interface is a 7.0" color touch-sensitive LCD with 800×480 resolution. Network options include CAN bus for small networks and Ethernet for larger systems, enabling interconnection of multiple panels.
Product Features- EN54-2 & EN54-4 certified (LPCB and Applus)
- 7.0" color touch-sensitive LCD, 800×480 resolution
- 324 addresses per loop, up to 8 loops
- Supports up to 5,000 fire protection zones
- Night Mode time-range settings for operational flexibility
- Networkable: CAN bus (up to 60 FACPs) and Ethernet (up to 254 FACPs)
- Event logging for fire, fault, cause & effect (C&E) and operations—each category stores up to 10,000 records
Technical ParametersPower supply
Mains supply: 110V/230V AC (-15%, +10%), 50Hz/60Hz
Mains fuse: T4A 250V
Operating voltage: 28V ±0.5V DC
Recommended mains cable: standard black mains cable, 1 mm²
Power rating: Imax.a = 3.1A; Imax.b = 5.55A; Imin = 0.3A
Max. battery supply current: 8A (when mains disconnected)
Max. charging current: 1A
Physical dimensions: 440 × 590 × 180 mm (with 18Ah battery); 440 × 590 × 230 mm (with 24Ah or 38Ah)
Max. internal resistance of battery: 1 Ω
Approx. weight (without battery): Standard 11 kg; Deep 13 kg
Battery fuse: 15A
Quiescent current (fully loaded): < 0.3A
Outputs
S.C.Out (+, -): 20–28V DC, max. 1A, end-of-line resistor 10 KΩ, cable 1–2.5 mm²
F.A.Out (+, -): 20–30V DC, max. 50 mA, end-of-line resistor 10 KΩ, cable 1–2.5 mm²
Fault Out (NC, COM, NO): contact capacity 2A @ 24V DC, cable 1–2.5 mm²
AUX 24V (+, -): 20–30V DC, max. 2A, cable 1–2.5 mm²
Technical Specifications- Model: SEC3008
- Standards: EN54-2 & EN54-4 (LPCB, Applus)
- Display: 7.0" color touch LCD, 800 × 480
- Addressable points: 324 per loop, up to 8 loops
- Zones supported: up to 5,000
- Network: CAN bus (up to 60 FACPs), Ethernet (up to 254 FACPs)
- Event log capacity: up to 10,000 records per category (fire, fault, C&E, operation)
- Mains input: 110V/230V AC (-15%/+10%), 50Hz/60Hz
- Operating voltage: 28V ±0.5V DC
- Max battery supply current: 8A (mains disconnected)
- Max charging current: 1A
- Outputs: S.C.Out 20–28V DC (1A), F.A.Out 20–30V DC (50 mA), AUX 24V (2A)
- Physical size: 440 × 590 × 180 mm (18Ah) / 440 × 590 × 230 mm (24Ah/38Ah)
- Weight (without battery): Standard 11 kg; Deep 13 kg