Product features- Two-part housing with an upper cover and a lower base for straightforward installation, commissioning and maintenance.
- On-board microcontroller samples data in real time, stores the most recent 144 historical points and supports trend/curve tracing of site conditions.
- Automatic compensation for temperature, humidity and dust accumulation to reduce drift.
Product infoThe C9030T Conventional Optical Smoke Detector is a two-wire switch-type smoke sensor. The detector uses a non-polar two-wire connection for compatibility with conventional switch-type alarm control panels and monitoring alarm systems. It can also be integrated into addressable fire alarm installations via a zone module.
Technical specifications- Standard: EN54-7
- Operating voltage: DC 24 V ±20%
- Operating current: Monitoring mode <50 µA; alarm mode 1 mA–20 mA (depends on loop current-limiting resistance)
- Indicator behaviour: Monitoring: red LED blinks once every 6 s; fault: blinks twice every 6 s; fire alarm: LED steady on
- Weight: approx. 120 g
- External dimensions: Diameter 100 mm; Height 58 mm (with base)
- Wiring: Non-polar two-bus (two-wire) system
- Operating environment: Indoor; temperature -10 °C to +55 °C; relative humidity ≤95% (40 °C ±2 °C, no condensation)
- Compatibility: Can be connected to addressable fire alarm systems via a zone module