OverviewThe JTY-GD-A30E point-type photoelectric smoke detector is an addressable, two-wire device designed for real-time smoke concentration monitoring and integration with compatible fire alarm control panels. It features an on-board microprocessor, in-situ electronic coding and local historical data storage for diagnostics and trend analysis.
Key features- Addressable via in-situ coder (selectable addresses 1–324).
- Real-time sampling processed by embedded MCU; stores up to 144 historical records for curve tracing and analysis.
- Temperature, humidity and dust-accumulation drift compensation; sensor fault detection with fault reporting to the control panel.
- Non-polarity two-wire bus for simplified wiring and maintenance.
- Modular design with removable upper/lower covers and independent base for easy installation, commissioning and service.
Applications- Suitable for restaurants, hotels, educational buildings, office buildings, computer rooms, communication rooms, libraries, archives and similar industrial or commercial facilities.
- Not recommended for locations with heavy dust, persistent water mist, steam or oil mist that produce smoke under normal conditions.
Technical specifications- Standard: GB 4715-2005
- Wiring: Non-polarity two-wire bus
- Working current: Inspection <300uA; Alarm <1.5mA
- Weight: approx. 75 g
- Dimensions: Ø105 mm × H43 mm (with base)
- Installation height: ≤12 m
- Operating temperature: -10℃ to +55℃, RH ≤95% (40℃±2℃, without condensation)
- Coding: Electronic coding via in-situ coder; addresses 1–324 selectable
- Indicators: Monitoring — red indicator flashing; Alarm — red indicator steady on
- Coverage area: approx. 60 m² (refer to GB 50116-2013)
Installation & operation- Mount on the supplied independent base for straightforward installation, testing and maintenance.
- Connect to a compatible two-wire fire alarm control system using non-polarity wiring.
- Check LED indication: flashing red in monitoring mode, steady red in alarm.