AC/AC power supply DDL-15000A
mobileregulatedvariable-output

AC/AC power supply - DDL-15000A - Wuhan UHV Power Technology Co.,Ltd. - mobile / regulated / variable-output
AC/AC power supply - DDL-15000A - Wuhan UHV Power Technology Co.,Ltd. - mobile / regulated / variable-output
AC/AC power supply - DDL-15000A - Wuhan UHV Power Technology Co.,Ltd. - mobile / regulated / variable-output - image - 2
AC/AC power supply - DDL-15000A - Wuhan UHV Power Technology Co.,Ltd. - mobile / regulated / variable-output - image - 3
AC/AC power supply - DDL-15000A - Wuhan UHV Power Technology Co.,Ltd. - mobile / regulated / variable-output - image - 4
AC/AC power supply - DDL-15000A - Wuhan UHV Power Technology Co.,Ltd. - mobile / regulated / variable-output - image - 5
AC/AC power supply - DDL-15000A - Wuhan UHV Power Technology Co.,Ltd. - mobile / regulated / variable-output - image - 6
Add to favorites
Compare this product

Characteristics

Mounting / format
mobile
Type
AC/AC
Output
regulated, variable-output, adjustable
Network
three-phase
Protection
with overcurrent protection
Protection class
IP20
Applications
for industrial applications, laboratory
Secondary function
measuring device
Other characteristics
compact, programmable, high-power, digital, computer-controlled
Input voltage

Max.: 418 V

Min.: 342 V

Output voltage

Max.: 418 V

Min.: 0 V

Current

Max.: 1,000 A

Min.: 0 A

Power

40,000 W

Output frequency

Max.: 51 Hz

Min.: 49 Hz

Description

Product overview
The DDL-15000A is a three-phase automatic temperature rise test device for electrical equipment. It comprises a control panel and a current regulator and is intended for short-term or intermittent temperature-rise and load tests on 50 Hz switches, current transformers and similar apparatus in power plants, substations, manufacturers, research institutions and test laboratories.

Use conditions / main parameters
  • Supply voltage: AC 380 V ±10% (three-phase four-wire)
  • Frequency: 50 Hz ±2%
  • Rated total capacity: 40 kVA
  • Output current: AC 0–1000 A (three-phase)
  • Protection rating: IP20
  • Operating temperature: -10℃ to 40℃; relative humidity ≤80%
  • Insulation resistance: ≥20 MΩ


Equipment parameters and functions
  • Output waveform: standard sinusoidal wave; ripple factor <0.3%
  • Output display: digital ammeter and voltmeter; large 160×80 remote display for regulator/booster values
  • Current/voltage accuracy: ±(2% × reading + 1% × range)
  • Load effect on voltage: ≤1% of rated value (for change from zero to rated current)
  • Output mode: true RMS continuously adjustable
  • Stepless current adjustment, stable current rise and wide load range
  • Protection: overcurrent and overvoltage (primary overcurrent protection), emergency stop, interlocks
  • Power path switching logic with mutual locking and zero-position locking for the voltage regulator


Temperature inspection device
  • Measurement range: -250℃ to 2400℃; resolution 0.1℃
  • Temperature accuracy: 0–1000℃: ±(reading × 0.5% + 1)℃; -100–0℃: ±(reading × 0.5% + 2)℃
  • Display: 7-inch LCD, English interface; supports 1–24 channels
  • Isolation channel max voltage: 100 V (exceeding may damage the instrument)
  • Recording: up to 8000 records; recording interval ≥1 s; real-time curve display up to 30 hours
  • Thermocouple compatibility: configurable to match multiple sensor types
  • Power-off memory: stores set parameters for up to 5 days; fixed-point and inspection functions


Key features
  • Integrated control panel and current regulator for compact footprint
  • Digital readouts for current and voltage for straightforward recording
  • Fully digital protection settings and timing for precise overcurrent protection
  • Manual and automatic operation modes
  • Secondary open-circuit overvoltage protection on transformer to protect CT secondary
  • Special mechanical design to reduce eddy-current heating of brackets and enclosure
  • Mobility: four top lifting rings and wheels at base for handling
  • Automatic temperature inspection with real-time recording and curve display


Technical specifications
  • Model: DDL-15000A
  • Input voltage: AC 380 V ±10%, three-phase four-wire
  • Frequency: 50 Hz ±2%
  • Rated total capacity: 40 kVA
  • Output current range: AC 0–1000 A (three-phase)
  • Output waveform: sinusoidal, ripple <0.3%
  • Current/voltage accuracy: ±(2% × reading + 1% × range)
  • Temperature measurement range: -250℃ to 2400℃; resolution 0.1℃
  • Temperature channels: configurable 1–24
  • Recording capacity: up to 8000 sets; interval ≥1 s; real-time curve up to 30 hours
  • Protection level: IP20

Catalogs

No catalogs are available for this product.

See all of Wuhan UHV Power Technology Co.,Ltd.‘s catalogs

Other Wuhan UHV Power Technology Co.,Ltd. products

High Voltage Tester

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry
DirectIndustry is a marketplace that offers B2B players a complete experience, from product sourcing to purchase. DirectIndustry is an entity of VirtualExpo Group.