Product overviewThe DDL-15000A is a three-phase automatic temperature rise test device for electrical equipment. It comprises a control panel and a current regulator and is intended for short-term or intermittent temperature-rise and load tests on 50 Hz switches, current transformers and similar apparatus in power plants, substations, manufacturers, research institutions and test laboratories.
Use conditions / main parameters- Supply voltage: AC 380 V ±10% (three-phase four-wire)
- Frequency: 50 Hz ±2%
- Rated total capacity: 40 kVA
- Output current: AC 0–1000 A (three-phase)
- Protection rating: IP20
- Operating temperature: -10℃ to 40℃; relative humidity ≤80%
- Insulation resistance: ≥20 MΩ
Equipment parameters and functions- Output waveform: standard sinusoidal wave; ripple factor <0.3%
- Output display: digital ammeter and voltmeter; large 160×80 remote display for regulator/booster values
- Current/voltage accuracy: ±(2% × reading + 1% × range)
- Load effect on voltage: ≤1% of rated value (for change from zero to rated current)
- Output mode: true RMS continuously adjustable
- Stepless current adjustment, stable current rise and wide load range
- Protection: overcurrent and overvoltage (primary overcurrent protection), emergency stop, interlocks
- Power path switching logic with mutual locking and zero-position locking for the voltage regulator
Temperature inspection device- Measurement range: -250℃ to 2400℃; resolution 0.1℃
- Temperature accuracy: 0–1000℃: ±(reading × 0.5% + 1)℃; -100–0℃: ±(reading × 0.5% + 2)℃
- Display: 7-inch LCD, English interface; supports 1–24 channels
- Isolation channel max voltage: 100 V (exceeding may damage the instrument)
- Recording: up to 8000 records; recording interval ≥1 s; real-time curve display up to 30 hours
- Thermocouple compatibility: configurable to match multiple sensor types
- Power-off memory: stores set parameters for up to 5 days; fixed-point and inspection functions
Key features- Integrated control panel and current regulator for compact footprint
- Digital readouts for current and voltage for straightforward recording
- Fully digital protection settings and timing for precise overcurrent protection
- Manual and automatic operation modes
- Secondary open-circuit overvoltage protection on transformer to protect CT secondary
- Special mechanical design to reduce eddy-current heating of brackets and enclosure
- Mobility: four top lifting rings and wheels at base for handling
- Automatic temperature inspection with real-time recording and curve display
Technical specifications- Model: DDL-15000A
- Input voltage: AC 380 V ±10%, three-phase four-wire
- Frequency: 50 Hz ±2%
- Rated total capacity: 40 kVA
- Output current range: AC 0–1000 A (three-phase)
- Output waveform: sinusoidal, ripple <0.3%
- Current/voltage accuracy: ±(2% × reading + 1% × range)
- Temperature measurement range: -250℃ to 2400℃; resolution 0.1℃
- Temperature channels: configurable 1–24
- Recording capacity: up to 8000 sets; interval ≥1 s; real-time curve up to 30 hours
- Protection level: IP20