Current transformer MTCF-451440
dryDIN rail mountsurface-mount

Current transformer - MTCF-451440 - Lettel - dry / DIN rail mount / surface-mount
Current transformer - MTCF-451440 - Lettel - dry / DIN rail mount / surface-mount
Current transformer - MTCF-451440 - Lettel - dry / DIN rail mount / surface-mount - image - 2
Current transformer - MTCF-451440 - Lettel - dry / DIN rail mount / surface-mount - image - 3
Current transformer - MTCF-451440 - Lettel - dry / DIN rail mount / surface-mount - image - 4
Add to favorites
Compare this product

Characteristics

Type
current
Configuration
dry
Mounting
DIN rail mount, surface-mount
Norms
RoHS
Other characteristics
closed, precision
Primary current

40 A

Secondary current

Min.: 1 A

Max.: 5 A

Description

Presentation
The MTCF series current transformers combine measurement accuracy with simple integration. Closed-type unit for through-cable installation, designed for use with meters and metering units accepting a 5 A input.

Main features
  • Electrical: Primary current 40 A; secondary 5 A; accuracy class 1.
  • Physical: Cable aperture Ø14 mm; enclosure dimensions H65 × L46 × P40 mm; surface mounting or DIN-rail mounting (DIN adapter sold separately); sealable terminal covers.
  • Documentation available: MTCF series overview; full product manual.

Benefits
  • Compact footprint for easy panel or field integration.
  • Sealable terminal covers to reduce electrical hazards and tampering.

Standards and certifications
  • Compliances: CE, RoHS, REACh.
  • Applicable standards: IEC 61869-1 & 2, IEC 60044-1, BS 3938, IS 2705-1,2 & 3.

Available variants
  • Secondary 1 A option available on request.

Accessories
  • DIN-rail mounting base: reference MTCF-45-DIN (sold separately).

Compatibility and related products
  • To be used with meters or metering units that have a 5 A input.
  • Compatible with standard electrical meters and metering systems accepting a 5 A secondary.

Technical specifications
  • Model reference: MTCF-451440
  • Primary current: 40 A
  • Secondary current: 5 A
  • Accuracy class: 1
  • Cable aperture: Ø14 mm
  • Enclosure dimensions: H65 × L46 × P40 mm
  • Mounting: surface or DIN-rail (accessory MTCF-45-DIN)
  • Sealable terminal covers
  • Compliances: CE, RoHS, REACh
  • Standards: IEC 61869-1 & 2, IEC 60044-1, BS 3938, IS 2705
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.