OverviewThe NT 100-CO-CO is a CANopen gateway that performs protocol conversion between two CANopen networks. It supports master and slave roles, integrates a subordinate CANopen trunk and the licensed Master functionality is unrestricted. The device is based on a netX / netX 100 communication controller and is designed for DIN-rail mounting in industrial automation environments. A memory card slot enables firmware and configuration backup and rapid device exchange.
Highlights- Integrates a subordinate CANopen network trunk
- Master for up to 126 CANopen nodes
- Shortest I/O data conversion period < 10 ms
- Device exchange in seconds via removable memory card
- Loadable firmware for flexible additional conversions
- Diagnostic and configuration interface via USB
Protocols supported- CANopen Master
- CANopen Slave
Technical data (excerpt)Product name: NT 100-CO-CO
Part number: 1716.160
Brief description: Gateway CANopen to CANopen
Communication controller: netX / netX 100
Integrated memory: RAM: 8 MB SDRAM · FLASH: 4 MB serial Flash
Memory card: SD or MMC card, max. 2 GByte
Power supply: 24 V DC ± 6 V
Maximum current at 24 V (typically): 130 mA · Typical power consumption: 3.2 W
Power connector: Mini-COMBICON, 2-pin · Reverse voltage protection: yes
UL requirement: For UL compliant usage: Device shall be supplied by an isolated voltage source
Communication interface X2: CANopen · Interface type: ISO 11898, optically isolated · Connector: D-Sub, plug, 9-pin
Communication interface X3: CANopen · Interface type: ISO 11898, optically isolated · Connector: D-Sub, plug, 9-pin
Diagnostic interface: USB · Connector: Mini-USB, 5-pin
Displays: LED displays (SYS system status · APL application status · CAN communication status Duo LED red/green)
Operating elements: Network address (2 rotary switches)
Permitted ambient conditions: Ambient temperature (operation) 0 … +60 °C · Humidity: no condensation permitted · Pollution degree: For UL-compliant usage: Device must be used in a pollution degree 2 environment · Altitude: 0 … 2000 m
Device dimensions (L x W x H): 100 x 52 x 70 mm (without connector) · Weight: appr. 150 g · Degree of protection: IP 20 · Mounting: on DIN rail EN 60715
Configuration software: SYCON.net
Conformity: RoHS: Yes · UL certification: The device is UL 508 certified · UL-File No E334100
Conformance with EMC directives: CE sign: Yes · UKCA sign: Yes · Emission: CISPR 11 Class A · Immunity: EN 61131-2 / BS EN 61131-2
Technical specifications- Product: NT 100-CO-CO (Gateway CANopen to CANopen)
- Part number: 1716.160
- Controller: netX 100
- Memory: 8 MB SDRAM, 4 MB serial Flash, SD/MMC up to 2 GByte
- Power: 24 V DC ±6 V, typical consumption 3.2 W, reverse voltage protection
- Interfaces: two CANopen channels (ISO 11898, optically isolated, D-Sub 9-pin), USB diagnostic (Mini-USB)
- LED status indicators and rotary network address switches
- Operating range: 0 … +60 °C, no condensation
- Dimensions / Mounting: 100 x 52 x 70 mm, DIN rail EN 60715, IP20
- Approvals / Compliance: RoHS, CE, UKCA, UL 508 (UL-File No E334100)