Communication gateway NT 100-RE-EN
industrialEthernetEtherNet/IP

Communication gateway - NT 100-RE-EN - Hilscher - industrial / Ethernet / EtherNet/IP
Communication gateway - NT 100-RE-EN - Hilscher - industrial / Ethernet / EtherNet/IP
Add to favorites
Compare this product

Characteristics

Type
communication, industrial
Network
Ethernet, EtherNet/IP, Modbus TCP, ProfiNet, EtherCAT, Powerlink, Sercos III
Other characteristics
DIN rail, IP20, 2 port
Transfer rate

Max.: 100 b/s

Min.: 10 b/s

Description

Overview
netTAP 100 is a communication gateway that links networks and performs protocol conversions between a Real-Time Ethernet protocol (2-port) and fieldbus or serial automation protocols. It can also convert between two fieldbus protocols or between a fieldbus and a serial protocol. Licensed Master functionality is unrestricted. A removable memory card slot enables fast device exchange and storage of firmware and configuration.

Highlights
  • Integrates a subordinate Real-Time Ethernet network into another Ethernet system and vice versa
  • Master capacity: up to 200 EtherCAT slaves, 128 PROFINET IO devices, 64 EtherNet/IP adapters, 511 Sercos slaves
  • Shortest I/O conversion period: < 10 ms
  • Device replacement in seconds via memory card load
  • Loadable firmware for flexible conversion scenarios
  • Diagnosis and configuration via USB interface


Supported protocols
  • Ethernet
  • Sercos Master/Slave
  • PROFINET IO-Controller / IO-Device
  • EtherNet/IP Scanner / Adapter
  • EtherCAT Master / Slave
  • POWERLINK Controlled Node
  • Modbus/TCP Server & Client


Technical data (extracted)
  • Product name: NT 100-RE-EN
  • Part number: 1712.110
  • Brief description: Gateway Real-Time-Ethernet to Ethernet
  • Communication controller: netX 100
  • Memory: 8 MB SDRAM; 4 MB serial Flash; SD/MMC slot (max. 2 GB)
  • Supply voltage: 24 V DC ±6 V
  • Typical current at 24 V: 130 mA
  • Typical power consumption: 3.2 W
  • Power connector: Mini-COMBICON, 2-pin; reverse voltage protection: yes
  • Power requirement (UL): isolated voltage source for UL-compliant usage
  • Ethernet interfaces: X2 = 2 × RJ45 (100BASE-TX/10BASE-T, isolated); X3 = 1 × RJ45
  • Diagnostic interface: Mini-USB (5-pin)
  • LEDs: SYS, APL, LINK, ACT (status LEDs)
  • Operating conditions: 0 … +60 °C; no condensation; altitude 0 … 2000 m; pollution degree 2 (UL)
  • Dimensions: 100 × 52 × 70 mm (without connector); weight ≈ 150 g; IP20; DIN-rail mounting
  • Configuration software: SYCON.net
  • Certifications: RoHS, CE, UKCA, UL 508 (UL-File No E334100)
  • EMC: CISPR 11 Class A; immunity per EN 61131-2; ESD ±8 kV air / ±4 kV contact

Catalogs

No catalogs are available for this product.

See all of Hilscher‘s catalogs

Exhibitions

Meet this supplier at the following exhibition(s):

CIBUS TEC
CIBUS TEC

27-30 Oct 2026 PARMA (Italy)

  • More information

    Other Hilscher products

    Gateways & Switches for Industrial Communication

    *Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.